BLDG-HVAC-MIB DEFINITIONS ::= BEGIN
IMPORTS
    MODULE-IDENTITY, Counter32,
    Gauge32, OBJECT-TYPE, Unsigned32, experimental
        FROM SNMPv2-SMI
    MODULE-COMPLIANCE, OBJECT-GROUP
       FROM SNMPv2-CONF
    TEXTUAL-CONVENTION,
    TimeStamp, RowStatus, StorageType
        FROM SNMPv2-TC
    SnmpAdminString
        FROM SNMP-FRAMEWORK-MIB;
 
 
bldgHVACMIB MODULE-IDENTITY
    LAST-UPDATED "200303270000Z"
    ORGANIZATION "SNMPCONF working group
                  E-mail: snmpconf@snmp.com"
    CONTACT-INFO
        "Jon Saperia
        Postal:     JDS Consulting
                    174 Chapman Street
                    Watertown, MA 02472
                    U.S.A.
        Phone:      +1 617 744 1079
        E-mail:     saperia@jdscons.com
 
        Wayne Tackabury
        Postal:     Gold Wire Technology
                    411 Waverley Oaks Rd.
                    Waltham, MA 02452
                    U.S.A.
        Phone:      +1 781 398 8800
        E-mail:     wayne@goldwiretech.com
 
 
 
        Michael MacFaden
        Postal:     Riverstone Networks
                    5200 Great America Pkwy.
                    Santa Clara, CA 95054
                    U.S.A.
        Phone:      +1 408 878 6500
        E-mail:     mrm@riverstonenet.com
 
        David Partain
        Postal:     Ericsson AB
                    P.O. Box 1248
                    SE-581 12  Linkoping
                    Sweden
        E-mail:     David.Partain@ericsson.com"
    DESCRIPTION
        "This example MIB module defines a set of management objects
        for heating ventilation and air conditioning systems.  It
        also includes objects that can be used to create policies
        that are applied to rooms.  This eliminates the need to send
        per-instance configuration commands to the system.
 
        Copyright (C) The Internet Society (2003).  This version of
        this MIB module is part of RFC 3512; see the RFC itself for
        full legal notices."
 
    REVISION "200303270000Z"
    DESCRIPTION
        "Initial version of BLDG-HVAC-MIB as published in RFC 3512."
    ::= { experimental 122 }
 
bldgHVACObjects         OBJECT IDENTIFIER ::= { bldgHVACMIB 1 }
bldgConformance         OBJECT IDENTIFIER ::= { bldgHVACMIB 2 }
 
--
-- Textual Conventions
--
 
BldgHvacOperation  ::= TEXTUAL-CONVENTION
    STATUS             current
    DESCRIPTION
        "Operations supported by a heating and cooling system.
        A reference to underlying general systems would go here."
    SYNTAX      INTEGER {
                         heat(1),
                         cool(2)
                }
--
-- HVAC Objects Group
 
 
 
--
 
bldgHVACTable    OBJECT-TYPE
    SYNTAX      SEQUENCE OF BldgHVACEntry
    MAX-ACCESS  not-accessible
    STATUS      current
    DESCRIPTION
        "This table is the representation and data control
        for building HVAC by each individual office.
        The table has rows for, and is indexed by a specific
        floor and office number.  Each such row includes
        HVAC statistical and current status information for
        the associated office.  The row also contains a
        bldgHVACCfgTemplate columnar object that relates the
        bldgHVACTable row to a row in the bldgHVACCfgTemplateTable.
        If this value is nonzero, then the instance in the row
        that has a value for how the HVAC has been configured
        in the associated template (bldgHVACCfgTeplateTable row).
        Hence, the bldgHVACCfgTeplateTable row contains the
        specific configuration values for the offices as described
        in this table."
    ::= { bldgHVACObjects 1 }
 
bldgHVACEntry  OBJECT-TYPE
    SYNTAX       BldgHVACEntry
    MAX-ACCESS   not-accessible
    STATUS       current
    DESCRIPTION
        "A row in the bldgHVACTable.  Each row represents a particular
        office in the building, qualified by its floor and office
        number.  A given row instance can be created or deleted by
        set operations  upon its bldgHVACStatus columnar
        object instance."
    INDEX { bldgHVACFloor, bldgHVACOffice }
        ::= { bldgHVACTable 1 }
 
BldgHVACEntry ::= SEQUENCE {
        bldgHVACFloor             Unsigned32,
        bldgHVACOffice            Unsigned32,
        bldgHVACCfgTemplate       Unsigned32,
        bldgHVACFanSpeed          Gauge32,
        bldgHVACCurrentTemp       Gauge32,
        bldgHVACCoolOrHeatMins    Counter32,
        bldgHVACDiscontinuityTime TimeStamp,
        bldgHVACOwner             SnmpAdminString,
        bldgHVACStorageType       StorageType,
        bldgHVACStatus            RowStatus
        }
 
 
 
bldgHVACFloor    OBJECT-TYPE
    SYNTAX      Unsigned32 (1..1000)
    MAX-ACCESS  not-accessible
    STATUS      current
    DESCRIPTION
        "This portion of the index indicates the floor of the
         building.  The ground floor is considered the
         first floor.  For the purposes of this example,
         floors under the ground floor cannot be
         controlled using this MIB module."
    ::= { bldgHVACEntry 1 }
 
bldgHVACOffice    OBJECT-TYPE
    SYNTAX      Unsigned32 (1..2147483647)
    MAX-ACCESS  not-accessible
    STATUS      current
    DESCRIPTION
        "This second component of the index specifies the
        office number."
    ::= { bldgHVACEntry 2 }
 
bldgHVACCfgTemplate  OBJECT-TYPE
    SYNTAX          Unsigned32
    MAX-ACCESS      read-create
    STATUS          current
    DESCRIPTION
        "The index (bldgHVACCfgTemplateIndex instance)
        of an entry in the 'bldgHVACCfgTemplateTable'.
        The bldgHVACCfgTable row instance referenced
        is a pre-made configuration 'template'
        that represents the configuration described
        by the bldgHVACCfgTemplateInfoDescr object.  Note
        that not all configurations will be under a
        defined template.  As a result, a row in this
        bldgHVACTable may point to an entry in the
        bldgHVACCfgTemplateTable that does not in turn
        have a reference (bldgHVACCfgTemplateInfo) to an
        entry in the bldgHVACCfgTemplateInfoTable.  The
        benefit of this approach is that all
        configuration information is available in one
        table whether all elements in the system are
        derived from configured templates or not.
 
        Where the instance value for this colunmar object
        is zero, this row represents data for an office
        whose HVAC status can be monitored using the
        read-only columnar object instances of this
        row, but is not under the configuration control
 
 
 
        of the agent."
    ::= { bldgHVACEntry 3 }
 
bldgHVACFanSpeed  OBJECT-TYPE
    SYNTAX            Gauge32
    UNITS             "revolutions per minute"
    MAX-ACCESS        read-only
    STATUS            current
    DESCRIPTION
        "Shows the revolutions per minute of the fan.  Fan speed
        will vary based on the difference between
        bldgHVACCfgTemplateDesiredTemp and bldgHVACCurrentTemp.  The
        speed is measured in revolutions of the fan blade per minute."
    ::= { bldgHVACEntry 4 }
 
bldgHVACCurrentTemp  OBJECT-TYPE
    SYNTAX            Gauge32
    UNITS             "degrees in celsius"
    MAX-ACCESS        read-only
    STATUS            current
    DESCRIPTION
        "The current measured temperature in the office.  Should
        the current temperature be measured at a value of less
        than zero degrees celsius, a read of the instance
        for this object will return a value of zero."
    ::= { bldgHVACEntry 5 }
 
bldgHVACCoolOrHeatMins  OBJECT-TYPE
    SYNTAX            Counter32
    UNITS             "minutes"
    MAX-ACCESS        read-only
    STATUS            current
    DESCRIPTION
        "The total number of heating or cooling minutes that have
        been consumed since the row was activated.  Notice that
        whether the minutes represent heating or cooling is a
        function of the configuration of this row.  If the system
        is re-initialized from a cooling to heating function or
        vice versa, then the counter would start over again.  This
        effect is similar to a reconfiguration of some network
        interface cards.  When parameters that impact
        configuration are changed, the subsystem must be
        re-initialized.  Discontinuities in the value of this counter
        can occur at re-initialization of the management system,
        and at other times as indicated by the value of
        bldgHVACDiscontinuityTime."
    ::= { bldgHVACEntry 6 }
 
 
 
 
bldgHVACDiscontinuityTime OBJECT-TYPE
    SYNTAX      TimeStamp
    MAX-ACCESS  read-only
    STATUS      current
    DESCRIPTION
        "The value of sysUpTime on the most recent occasion at which
        any heating or cooling operation for the office designated
        by this row instance experienced a discontinuity.  If
        no such discontinuities have occurred since the last re-
        initialization of the this row, then this object contains a
        zero value."
    ::= { bldgHVACEntry 7 }
 
bldgHVACOwner  OBJECT-TYPE
    SYNTAX            SnmpAdminString
    MAX-ACCESS        read-create
    STATUS            current
    DESCRIPTION
        "The identity of the operator/system that
        last modified this entry.  When a new entry
        is created, a valid SnmpAdminString must
        be supplied.  If, on the other hand, this
        entry is populated by the agent 'discovering'
        unconfigured rooms, the empty string is a valid
        value for this object."
    ::= { bldgHVACEntry 8 }
 
bldgHVACStorageType  OBJECT-TYPE
    SYNTAX            StorageType
    MAX-ACCESS        read-create
    STATUS            current
    DESCRIPTION
        "The persistence of this row of the table in system storage,
        as it pertains to permanence across system resets.  A columnar
        instance of this object with value 'permanent' need not allow
        write-access to any of the columnar object instances in the
        containing row."
    ::= { bldgHVACEntry 9  }
 
bldgHVACStatus  OBJECT-TYPE
    SYNTAX            RowStatus
    MAX-ACCESS        read-create
    STATUS            current
    DESCRIPTION
        "Controls and reflects the creation and activation status of
        a row in this table.
 
        No attempt to modify a row columnar object instance value in
 
 
 
        the bldgHVACTable should be issued while the value of
        bldgHVACStatus is active(1).  Should an agent receive a SET
        PDU attempting such a modification in this state, an
        inconsistentValue error should be returned as a result of
        the SET attempt."
    ::= { bldgHVACEntry 10 }
--
-- HVAC Configuration Template Table
--
 
bldgHVACCfgTemplateInfoTable  OBJECT-TYPE
    SYNTAX      SEQUENCE OF BldgHVACCfgTemplateInfoEntry
    MAX-ACCESS  not-accessible
    STATUS      current
    DESCRIPTION
        "This table provides unique string identification for
        HVAC templates in a network.  If it were necessary to
        configure rooms to deliver a particular quality of climate
        control with regard to cooling or heating, the index string
        of a row in this table could be the template name.
        The bldgHVACCfgCfgTemplateInfoDescription
        contains a brief description of the template service objective
        such as: provides summer cooling settings for executive
        offices.  The bldgHVACCfgTemplateInfo in the
        bldgHVACCfgTemplateTable will contain the pointer to the
        relevant row in this table if it is intended that items
        that point to a row in the bldgHVACCfgTemplateInfoTable be
        identifiable as being under template control though this
        mechanism."
 
    ::= { bldgHVACObjects 2 }
 
bldgHVACCfgTemplateInfoEntry  OBJECT-TYPE
    SYNTAX       BldgHVACCfgTemplateInfoEntry
    MAX-ACCESS   not-accessible
    STATUS       current
    DESCRIPTION
        "Each row represents a particular template and
        description.  A given row instance can be created or
        deleted by set operations upon its
        bldgHVACCfgTemplateInfoStatus columnar object
        instance."
    INDEX { bldgHVACCfgTemplateInfoIndex }
    ::= { bldgHVACCfgTemplateInfoTable 1 }
 
BldgHVACCfgTemplateInfoEntry ::= SEQUENCE {
        bldgHVACCfgTemplateInfoIndex          Unsigned32,
        bldgHVACCfgTemplateInfoID             SnmpAdminString,
 
 
 
        bldgHVACCfgTemplateInfoDescr          SnmpAdminString,
        bldgHVACCfgTemplateInfoOwner          SnmpAdminString,
        bldgHVACCfgTemplateInfoStatus         RowStatus,
        bldgHVACCfgTemplateInfoStorType       StorageType
        }
 
bldgHVACCfgTemplateInfoIndex   OBJECT-TYPE
       SYNTAX       Unsigned32 (1..2147483647)
       MAX-ACCESS   not-accessible
       STATUS       current
       DESCRIPTION
           "The unique index to a row in this table."
        ::= { bldgHVACCfgTemplateInfoEntry 1 }
 
bldgHVACCfgTemplateInfoID  OBJECT-TYPE
    SYNTAX       SnmpAdminString
    MAX-ACCESS   read-create
    STATUS       current
    DESCRIPTION
        "Textual identifier for this table row, and, consequently
        the template.  This should be a unique name within
        an administrative domain for a particular template so that
        all systems in a network that are under the same template
        can have the same 'handle' (e.g., 'Executive Offices',
        'Lobby Areas')."
    ::= { bldgHVACCfgTemplateInfoEntry 2 }
 
 
bldgHVACCfgTemplateInfoDescr   OBJECT-TYPE
    SYNTAX       SnmpAdminString
    MAX-ACCESS   read-create
    STATUS       current
    DESCRIPTION
        "A general description of the template.  One example might
        be - Controls the cooling for offices on higher floors
        during the summer."
    ::= { bldgHVACCfgTemplateInfoEntry 3 }
 
bldgHVACCfgTemplateInfoOwner  OBJECT-TYPE
    SYNTAX            SnmpAdminString
    MAX-ACCESS        read-create
    STATUS            current
    DESCRIPTION
        "The identity of the operator/system that last modified
        this entry."
    ::= { bldgHVACCfgTemplateInfoEntry 4 }
 
bldgHVACCfgTemplateInfoStatus  OBJECT-TYPE
 
 
 
    SYNTAX            RowStatus
    MAX-ACCESS        read-create
    STATUS            current
    DESCRIPTION
        "The activation status of this row.
 
        No attempt to modify a row columnar object instance value in
        the bldgHVACCfgTemplateInfo Table should be issued while the
        value of bldgHVACCfgTemplateInfoStatus is active(1).
        Should an agent receive a SET PDU attempting such a modification
        in this state, an inconsistentValue error should be returned as
        a result of the SET attempt."
    ::= { bldgHVACCfgTemplateInfoEntry 5 }
 
bldgHVACCfgTemplateInfoStorType   OBJECT-TYPE
    SYNTAX            StorageType
    MAX-ACCESS        read-create
    STATUS            current
    DESCRIPTION
        "The persistence of this row of the table in system storage,
         as it pertains to permanence across system resets.  A columnar
        instance of this object with value 'permanent' need not allow
        write-access to any of the columnar object instances in the
        containing row."
    ::= { bldgHVACCfgTemplateInfoEntry 6  }
 
--
-- HVAC Configuration Template Table
--
bldgHVACCfgTemplateTable    OBJECT-TYPE
    SYNTAX      SEQUENCE OF BldgHVACCfgTemplateEntry
    MAX-ACCESS  not-accessible
    STATUS      current
    DESCRIPTION
        "This table contains the templates, which
        can be used to set defaults that will
        be applied to specific offices.  The application
        of those values is accomplished by having a row
        instance of the bldgHVACTable reference a row of
        this table (by the value of the former's
        bldgHVACCfgTemplate columnar instance).  Identifying
        information concerning a row instance of this table
        can be found in the columnar data of the row instance
        of the bldgHVACCfgTemplateInfoTable entry referenced
        by the bldgHVACCfgTemplateInfo columnar object of
        this table."
    ::= { bldgHVACObjects 3 }
 
 
 
 
bldgHVACCfgTemplateEntry  OBJECT-TYPE
    SYNTAX       BldgHVACCfgTemplateEntry
    MAX-ACCESS   not-accessible
    STATUS       current
    DESCRIPTION
        "Each row represents a single set of template parameters
        that can be applied to selected instances - in this case
        offices.  These policies will be turned on and off by the
        policy module through its scheduling facilities.
 
        A given row instance can be created or
        deleted by set operations upon its
        bldgHVACCfgTemplateStatus columnar object instance."
    INDEX { bldgHVACCfgTemplateIndex }
    ::= { bldgHVACCfgTemplateTable 1 }
 
BldgHVACCfgTemplateEntry ::= SEQUENCE {
        bldgHVACCfgTemplateIndex           Unsigned32,
        bldgHVACCfgTemplateDesiredTemp     Gauge32,
        bldgHVACCfgTemplateCoolOrHeat      BldgHvacOperation,
        bldgHVACCfgTemplateInfo            Unsigned32,
        bldgHVACCfgTemplateOwner           SnmpAdminString,
        bldgHVACCfgTemplateStorage         StorageType,
        bldgHVACCfgTemplateStatus          RowStatus
}
 
bldgHVACCfgTemplateIndex    OBJECT-TYPE
    SYNTAX      Unsigned32 (1..2147483647)
    MAX-ACCESS  not-accessible
    STATUS      current
    DESCRIPTION
        "A unique value for each defined template in this
        table.  This value can be referenced as a row index
        by any MIB module that needs access to this information.
        The bldgHVACCfgTemplate will point to entries in this
        table."
    ::= { bldgHVACCfgTemplateEntry 1 }
 
bldgHVACCfgTemplateDesiredTemp OBJECT-TYPE
    SYNTAX            Gauge32
    UNITS             "degrees in celsius"
    MAX-ACCESS        read-create
    STATUS            current
    DESCRIPTION
        "This is the desired temperature setting.  It might be
        changed at different times of the day or based on
        seasonal conditions.  It is permitted to change this value
        by first moving the row to an inactive state, making the
 
 
 
        change and then reactivating the row."
    ::= { bldgHVACCfgTemplateEntry 2 }
 
bldgHVACCfgTemplateCoolOrHeat  OBJECT-TYPE
    SYNTAX             BldgHvacOperation
    MAX-ACCESS         read-create
    STATUS             current
    DESCRIPTION
        "This controls the heating and cooling mechanism and is
        set-able by building maintenance.  It is permitted to
        change this value by first moving the row to an inactive
        state, making the change and then reactivating the row."
    ::= { bldgHVACCfgTemplateEntry 3 }
 
bldgHVACCfgTemplateInfo OBJECT-TYPE
    SYNTAX             Unsigned32
    MAX-ACCESS         read-create
    STATUS             current
    DESCRIPTION
        "This object points to a row in the
        bldgHVACCfgTemplateInfoTable.  This controls the
        heating and cooling mechanism and is set-able by
        building maintenance.  It is permissible to change
        this value by first moving the row to an inactive
        state, making the change and then reactivating
        the row.  A value of zero means that this entry
        is not associated with a named template found
        in the bldgHVACCfgTemplateInfoTable."
    ::= { bldgHVACCfgTemplateEntry 4 }
 
bldgHVACCfgTemplateOwner  OBJECT-TYPE
    SYNTAX            SnmpAdminString
    MAX-ACCESS        read-create
    STATUS            current
    DESCRIPTION
        "The identity of the administrative entity
        that created this row of the table."
    ::= { bldgHVACCfgTemplateEntry 5 }
 
bldgHVACCfgTemplateStorage  OBJECT-TYPE
    SYNTAX            StorageType
    MAX-ACCESS        read-create
    STATUS            current
    DESCRIPTION
        "The persistence of this row of the table across
         system resets.  A columnar instance of this object with
         value 'permanent' need not allow write-access to any
         of the columnar object instances in the containing row."
 
 
 
    ::= { bldgHVACCfgTemplateEntry 6 }
 
bldgHVACCfgTemplateStatus  OBJECT-TYPE
    SYNTAX            RowStatus
    MAX-ACCESS        read-create
    STATUS            current
    DESCRIPTION
        "The activation status of this row of the table.
 
        No attempt to modify a row columnar object instance value in
        the bldgHVACCfgTemplateTable should be issued while the
        value of bldgHVACCfgTemplateStatus is active(1).
        Should an agent receive a SET PDU attempting such a modification
        in this state, an inconsistentValue error should be returned as
        a result of the SET attempt."
    ::= { bldgHVACCfgTemplateEntry 7 }
 
--
-- Conformance Information
--
 
bldgCompliances  OBJECT IDENTIFIER ::= { bldgConformance 1 }
bldgGroups       OBJECT IDENTIFIER ::= { bldgConformance 2 }
 
-- Compliance Statements
 
bldgCompliance MODULE-COMPLIANCE
    STATUS current
    DESCRIPTION
        "The requirements for conformance to the BLDG-HVAC-MIB.  The
         bldgHVACObjects group must be implemented to conform to the
         BLDG-HVAC-MIB."
    MODULE -- this module
 
    GROUP bldgHVACObjectsGroup
    DESCRIPTION
        "The bldgHVACObjects is mandatory for all systems that
        support HVAC systems."
    ::= { bldgCompliances 1 }
 
bldgHVACObjectsGroup OBJECT-GROUP
    OBJECTS {
        bldgHVACCfgTemplate,
        bldgHVACFanSpeed, bldgHVACCurrentTemp,
        bldgHVACCoolOrHeatMins, bldgHVACDiscontinuityTime,
        bldgHVACOwner, bldgHVACStatus,
        bldgHVACStorageType, bldgHVACCfgTemplateInfoID,
        bldgHVACCfgTemplateInfoDescr, bldgHVACCfgTemplateInfoOwner,
 
 
 
        bldgHVACCfgTemplateInfoStatus,
        bldgHVACCfgTemplateInfoStorType,
        bldgHVACCfgTemplateDesiredTemp,
        bldgHVACCfgTemplateCoolOrHeat,
        bldgHVACCfgTemplateInfo,
        bldgHVACCfgTemplateOwner,bldgHVACCfgTemplateStorage,
        bldgHVACCfgTemplateStatus
    }
    STATUS current
    DESCRIPTION
        "The bldgHVACObjects Group."
    ::= { bldgGroups 1 }
 
END